⚙️ I. Typical Application Scenarios & Threshold References
Fire Protection Systems
Standard Type: Activation range 0.035–0.05MPa (pump start pressure)
Preaction Systems: Lower sensitivity range 0.03–0.05MPa
Rail Transportation
Train braking system trigger point: 3.8 Bar (≈ 0.38MPa), cuts off traction enable when line pressure drops below this value.
Industrial Equipment
Reference Point: Typically 0.5MPa (calibrated at standard atmospheric pressure)
Action Threshold: Common setting 0.8MPa (adjusted via precision wrench)
Hysteresis Range: Maintain 0.05–0.2MPa (too small causes frequent cycling; too large reduces accuracy)
🔧 II. Adjustment Procedures
Mechanical Pressure Switches
Increasing Threshold:
- Loosen adjustment screw counterclockwise
- Pressurize to target value
- Tighten clockwise until contacts activate (audible "click")
Differential Setting:
Lower limit = Upper limit (e.g., 0.8MPa) - Desired differential (e.g., 0.3MPa → 0.5MPa)
Electronic Pressure Switches
Modify setpoint via menu interface (long-press function key for calibration mode on some models)
PID algorithm optimization for dynamic conditions
📊 III. Key Parameter Standards
Parameter Recommended Range Application Example
Safety Margin ≥1.2× operating pressure Rated 10MPa switch ≤8MPa test
Hysteresis Rate 5%–15% of full scale Food machinery: 5–8%, Industrial: 10–15%
Action Error ≤±1.0% FS 10MPa scale error ≤0.1MPa
️ IV. Critical Prohibitions
Never exceed rated range: Test pressure ≤80% of rated value
Avoid insufficient hysteresis: Causes equipment cycling → reduced lifespan
Power off before adjustment: Always disconnect system power
Post-adjustment Validation: Cycle pressure 3×; actuation deviation ≤50% of accuracy class
(Multimedia content suggestions preserved as placeholders)